EnergyCell 525FLA
|
Cells Per Unit:
|
3
|
Nominal Voltage
|
6VDC
|
Amp Hour Capacity to 1.75 Volts Per Cell at 20° C (24 hour Rate)
|
445 |
Cycle Life (50% DOD, 1.75VPC)
|
1550 |
Absorb Voltage (25° C)
|
7.26VDC
|
Absorb Time
|
2 hours
|
Float Voltage (25° C)
|
6.75VDC
|
Float Time
|
= absorb time
|
Equalize Charge Frequency
|
Equalize charge every 30 days, systems that are regularly discharged below 50% of stored capacity should be equalized every 14 days.
|
Re-Bulk Voltage
|
12VDC/ 24VDC/ 48VDC
|
Re-Float Voltage
|
12.5VDC/ 25VDC/ 50VDC
|
Maximim Charge Current (Per Battery)
|
100A
|
Operating Temperature Range
(w/ Temperature Compensation)
|
-40° to 120°F (-4 to 49°C)
|
Optimal Operating Temperature Range
|
-40° to 80°F (4 to 27°C)
|
Temp-Comp Factor (Charging)
|
3mV per °C per cell
|
Self-Discharge Time
|
Fully charged batteries that are stored at a temperature of 80°F (27°C) will self discharge at a rate of 3.5% per week.
|
Terminal Type
|
Standard type with stainless steel
|
Terminal Hardware Initial Torque
|
Stainless thread, 100 to 120in-lbs (11 to 14Nm)
|
Weight
|
112 lbs / 55.3 kg
|
Dimensions
(H x D x W)
|
16.13" H x 7.19" D x 12.38" W
|
Warranty
|
2 years full replacement
|
Equalize Voltage
|
7.74VDC
|
Specific Gravity
|
Full charge specific gravity (100% state of charge): 1.125 |
Vent Cap
|
Bayonet
|
PROeye Electrolyte Level Indicator
|
No
|