SolarEdge > 50,000 Watt 208V Three Phase Synergy Inverter with AC RSD, DC Safety Switch and AC/DC SPD
NOTE: Requires three Synergy Units SE-SUK-USR0INNN4, purchased separately
)
Specifications
Model
|
SE50K-US02IBNZ4
|
Series
|
SolarEdge Synergy Inverters
|
Manufacturer
|
SolarEdge
|
Mechanical / Installation Specifications
Type
|
Grid-Tie
|
Number of Units
|
2
|
AC Output Cable
|
Cable gland — diameter 22-32; PE gland diameter 10-16
|
DC Input
|
6 strings, 4-10mm2 DC wire, gland outer diameter 5-10mm /
3 MC4 pairs per unit
|
AC Output Wire
|
Aluminum or Copper; L, N: Up to 70, PE: Up to 35
|
Dimensions (H x W x D)
|
Primary Unit: 940 x 315 x 260 mm (37" x 12.4" x 10.24") ;
Secondary Unit: 540 x 315 x 260 mm (21.26" x 12.4" x 10.24"
|
Weight
|
Primary Unit: 48 kg; Secondary Unit: 45 kg
|
Operating Temperature Range
|
-40° C to +60° C
|
Cooling
|
Fans (user replaceable)
|
Noise
|
< 60 dBA
|
Protection Rating
|
IP65 — Outdoor and Indoor
|
Mounting
|
Bracket Provided
|
Shipping Method
|
Freight
|
Input (DC)
Maximum DC Power (Module STC), Inverter / Unit
|
67500 / 33750 W
|
Transformer-less, Ungrounded
|
Yes
|
Maximum Input Voltage
|
1000 VDC
|
Nominal DC Input Voltage
|
750 VDC
|
Maximum Input Current
|
2 x 37 ADC
|
Reverse-Polarity Protection
|
Yes
|
Ground-Fault Isolation Detection
|
350kΩ Sensitivity per Unit
|
Maximum Inverter Efficiency
|
98.3%
|
European Weighted Efficiency
|
98%
|
Nighttime Power Consumption
|
< 12W
|
Output (AC)
Nominal Output Power
|
50,000 V
|
Maximum AC Output Power
|
50,000 V
|
AC Output Voltage — Line to Line / Line to Neutral (Nominal)
|
380/220 ; 400/230 VAC
|
AC Output Voltage — Line to Line Range / Line to Neutral Range
|
304 - 437 / 176 - 253 ; 320 - 460 /184 - 264.5 VAC
|
AC Frequency
|
50/60 ± 5 Hz
|
Maximum Continuous Output Current (per Phase) @Vac,nom
|
76 A
|
Grids Supported — Three Phase
|
3 / N / PE (WYE with Neutral) V
|
Maximum Residual Current Injection
|
250 mA per unit
|
Utility Monitoring, Islanding Protection, Configurable Power Factor, Country Configurable Thresholds
|
Yes
|
Additional Features
Supported Communication Interfaces
|
RS485, Ethernet, GSM plug-in (optional)
|
RS485 Surge Protection
|
Built-In
|
Rapid Shutdown
|
Optional(6) (Automatic upon AC Grid Disconnect)
|
Connection Unit
DC Disconnect (optional)
|
1000V / 2 x 40A
|
Standard Compliance
Safety
|
IEC-62109, AS3100
|
Grid Connection Standards
|
VDE-AR-N-4105, G99, AS-4777,EN 50438 , CEI-021,VDE 0126-1-1, CEI-016, BDEW
|
Emissions
|
IEC61000-6-2, IEC61000-6-3 , IEC61000-3-11, IEC61000-3-12
|
RoHS
|
Yes
|
Features
- Easy two-person installation – each unit mounted separately, equipped with cables for simple connection between units
- Balance of System and labor reduction compared to using multiple smaller string inverters
- Independent operation of each unit enables higher uptime and easy serviceability
- No wasted ground area: wall/rail mounted or horizontally mounted under the modules (10 ̊ inclination)
- Built-in module-level monitoring with Ethernet or cellular GSM
- Fixed voltage inverter for superior efficiency (98.3%) and longer strings
- Integrated Connection Unit with optional integrated DC Safety Switch – eliminates the need for external DC isolators
- Built-in RS485 Surge Protection, to better withstand lightning events
- Advanced safety features - integrated arc fault protection and optional rapid shutdown
|
|
 |
 |
 |
 |
|
 |


|