100 kW 270/480 VAC, Three Phase Grid-Tie Inverter - with AC Automatic Rapid Shutdown, Connection Unit, DC Safety Switch and AFCI - Fixed Voltage
Specifications
Model
|
SE100KUS
(SE100K-USRP0BNU4)
|
Series
|
SetApp 3-Phase Inverter
|
Manufacturer
|
SolarEdge
|
Mechanical
Type
|
Grid-Tie
|
Operating Temperature Range
|
-40 to +140°F / -40° C to +60° C
|
Enclosure
|
NEMA 3R
|
Cooling
|
Fans (user replaceable)
|
Dimensions (W x H x D)
|
21" x 12.5" x 10.5"
|
Dimensions with Safety Switch (W x H x D)
|
Primary Unit: 37" x 12.5" x 10.5"
Secondary Unit: 21" x 12.5" x 10.5"
|
Weight
|
Primary Unit: 105.8 lbs
Secondary Unit: 99.2 lbs
|
Shipping Method
|
Freight
|
Input (DC)
Maximum DC Power (STC)
|
135,000 W
|
Transformer-less, Ungrounded
|
Yes
|
Maximum Input Voltage DC to Ground
|
500 V
|
Maximum Input Voltage DC+ to DC-
|
1000 V
|
Nominal Input Voltage DC to Ground
|
425 V
|
Nominal Input Voltage DC+ to DC-
|
4850 V
|
Max Input Current
|
120 ADC
|
Output (AC)
Rated AC Power Output
|
100,000 VA
|
Maximum AC Power Output
|
100,000 VA
|
AC Output Line Connections
|
4-wire WYE (L1-L2-L3-N) plus PE or 3 wire Delta
|
AC Output Voltage Minimum-Nominal-Maximum(1) (L-N)
|
244 - 277 - 305 VAC
|
AC Output Voltage Minimum-Nominal-Maximum(1) (L-L)
|
422.5 - 480 - 529 VAC
|
AC Frequency Min-Nom-Max
|
59.3 - 60 - 60.5 Hz
|
Maximum Continuous Output Current (per Phase) @208V
|
120 A
|
GFDI Threshold
|
1
|
Utility Monitoring, Islanding Protection, Configurable Power Factor,
Country Configurable Thresholds
|
Yes
|
Detailed Description
SolarEdge Three-Phase SetApp Inverters
The SolarEdge three phase inverter combines sophisticated digital control technology with efficient power conversion architecture to achieve superior solar power harvesting and best-in-class reliability. The fixed-voltage technology ensures the solar inverter is always working at its optimal input voltage over a wider range of string lengths and regardless of environmental conditions.
A proprietary data monitoring receiver has been integrated into the inverter and aggregates the power optimizer performance data from each PV module. This data can be transmitted to the web and accessed via the SolarEdge monitoring platform for performance analysis, fault detection and troubleshooting of PV systems.
Easy Inverter Commissioning with Inverter SetApp
The new range of SolarEdge three phase inverters have a smart new commissioning method. Inverter commissioning is done directly through a smartphone using the intuitive SetApp mobile application. Take your inverter commissioning to the next level. NOTE: SetApp Cellular or Zigbee compatible card must be used if applicable.
Features
- Easy two-person installation – each unit mounted separately, equipped with cables for simple connection between units
- Balance of System and labor reduction compared to using multiple smaller string inverters
- Independent operation of each unit enables higher uptime and easy serviceability
- No wasted ground area: wall/rail mounted, or horizontally mounted under the modules (10 ̊ inclination)
- Integrated arc fault protection and rapid shutdown for NEC 2014 and 2017, per article 690.11 and 690.12
- Built-in module-level monitoring with Ethernet or cellular GSM
- Fixed voltage inverter for superior efficiency (98.5%) and longer strings
- Integrated DC Safety Switch and optional surge protection
- Built-in RS485 Surge Protection, to better withstand lightning events