Specifications
Model
|
PRO480-8k
|
Series
|
ProHarvest
|
Manufacturer
|
Outback Power
|
Mechanical
Type
|
Commercial three-phase 480V String Inverter
|
Dimensions (W x H x D)
|
18.75" x 13.125" x 3"
|
Weight
|
24 lbs
|
Operating Temperature Range
|
-40° C to 65° C
|
Enclosure
|
NEMA6, IP67, Outdoor/Rooftop
|
Cooling
|
Natural convection, no fan
|
Communication
|
Powerline
|
Certifications
|
Listed to UL1741/IEEE 1547 (utility interactive) CSA C22.2 No. 107.1, FCC Part 15, meets the requirements of NEC 690.11
|
Warranty
|
10-year, optionally extendable
|
Shipping Method
|
Ground
|
Input (DC)
Max. Open Circuit Voltage
(per string)
|
1000 VDC
|
Full Power MPPT Range
(per string)
|
425 to 850 VDC
|
PV Start Voltage
|
200 VDC
|
DC Allowable Stacking Ratio
(total, 2 inputs combined)
|
Must not exceed 6.375 under any circumstances
|
DC Maximum Input
|
Current (per DC input): 10A
Short circuit current: 30A
|
DC Disconnect Means
|
DC connector has been evaluated and approved for use as the load-break disconnect required by the NEC (NEC section 690.17, allowed by the exception of meeting requirements specified in 690.33)
|
Output (AC)
AC Maximum
|
Continuous total output power (to 45°C): 8kW
Continuous output current (per phase): 9.6A Output overcurrent protection: 60A
|
AC Derate (40-65°C)
|
-150W per °C
|
AC Nominal Output Current (per phase
|
9.6 A
|
AC Three-Phase System Compatibility
|
480V Wye, three phases, neutral and ground
|
AC Voltage Range
(limits adjustable)
|
Phase to Phase
Minimum: 422V
Nominal: 480V
Maximum: 528V
Phase to Neutral
Minimum: 244V
Nominal: 277V
Maximum: 305V
|
AC Output Frequency Range
(limits adjustable)
|
Minimum: 59.3Hz Nominal: 60Hz Maximum: 60.5Hz
|
Power Factor
|
≥0.98
|
AC Upper Trip Limit
|
Frequency
Default (±1Hz): 59.3Hz
Adjustment (±1Hz): 57 to 59.3Hz
Clearing Time Default (±2 Cycles): 0.16s
Clearing Time Adjustment (±2 Cycles): 0.16 to 300s
Voltage (Phase to Neutral)
Default (±2%): 245V
Adjustment (±2%): 220 to 245V
Clearing Time Default (±2 Cycles): 2s
Clearing Time Adjustment (±2 Cycles): 1 to 20s
|
AC Lower Trip Limit
|
Frequency
Default (±1Hz): 60.5Hz
Adjustment (±1Hz): 60.5 to 62.0Hz
Clearing Time Default (±2 Cycles): 0.16s
Clearing Time Adjustment (±2 Cycles): 0.16 to 300s
Voltage (Phase to Neutral)
Default (±2%): 305V
Adjustment (±2%): 305 to 315V
Clearing Time Default (±2 Cycles): 1s
Clearing Time Adjustment (±2 Cycles): 1 to 20s
|
AC Reconnect Delay
|
Default: 5 min
Adjustment: 1 second to 10 min
|
AC Synchronization In-Rush Current
|
0 A
|
Maximum Output Fault Current and Duration
|
10 A, <0.5ms
|
AC Minimum Wire Gauge
(for grid connection)
|
14 AWG
|
AC Disconnect Means
|
The AC connector has been evaluated and approved for use as the load-break disconnect required by the NEC (NEC section 690.17, allowed by the exception of meeting requirements specified in 690.33)
|
Documentation
Features
- Rugged 3-phase 480V plug & play system
- Small and light (hand holdable, 24lb.)
- Non-isolated inverter for use with ungrounded DC systems
- 98.6% peak efficiency
- 200-850V MPP voltage range for 600V and 1,000V systems
- 8kW, full power MPP voltage 425-850V
- Two DC string inputs with independent monitoring and MPPT management
- Waterproof NEMA6, silent convection cooling
- Wide temperature range (-40 to 65°C)
- Compliant with NEC 690.11 arc detection
Applications
- Rooftop commercial: usable where other solutions just won’t work
such as coastal, desert and high altitude locations
- Car ports, parking and shade structures: can be mounted at any
orientation, under modules, on racking without extra strengthening
(clear of risk of liability from vandalism)
|
|
|
|
|
|
|